11.4 Cleaning of
Exhaust Systems
Upon inspection,
if found to be contaminated with deposits from grease-laden vapors, the entire
exhaust system shall be cleaned by a properly trained, qualified, and
certified company or person (s)
acceptable to the authority having jurisdiction in accordance with Section 11.3.
11.4.2
Hoods, grease removal
devices, fans, ducts, and other appurtenances shall be cleaned to bare metal
prior to surfaces becoming heavily contaminated with grease or oily sludge.
11.4.3
At the start of the cleaning process, electrical switches that could be
activated accidentally shall be locked out.
11.4.4
Components of the fire suppression system shall not be rendered inoperable
during the cleaning process.
11.4.5
Fire-extinguishing systems
shall be permitted to be rendered inoperable during the cleaning process where
serviced by properly trained and qualified persons in accordance with Section
11.3.
11.4.6
Flammable solvents or other flammable cleaning aids shall not be used.
11.4.7
Cleaning chemicals shall not
be applied on fusible links or other detection devices or the automatic
extinguishing system.
11.4.8
After the exhaust system is cleaned to bare metal, it shall not be coated with
powder or other substance.
11.4.9
All access panels (doors) and
cover plates shall be replaced.
11.4.10
Dampers and diffusers shall be positioned for proper airflow.
11.4.11
When cleaning procedures are
completed, all electrical switches and system components shall be returned to an
operable state.
11.4.12
When a vent cleaning service
is used, a certificate showing date of inspection or cleaning shall be
maintained on the premises.
11.4.13
After cleaning is completed,
the vent cleaning contractor shall place or display within the kitchen area a
label indicating the date cleaned and the name of the servicing company, and
areas not cleaned.
11.4.14
Where required, certificates of inspection and cleaning shall be submitted to
the authority having jurisdiction.
1.3.2
The authority having
jurisdiction shall determine compliance with this standard and authorize
equivalent deviations from it in all applications.
3.2.5 Shall.
Indicates a mandatory
requirement.
3.3.40 Solid Cooking
Fuel. Any solid,
organic, consumable fuel such as briquettes, mesquite, hardwood, or charcoal.
4.1.8
All interior surfaces of the exhaust system shall be accessible for cleaning and
inspection purposes.
6.2.3.3
Grease filters shall be arranged so that all exhaust air shall pass through the
grease filters.
14.1.6
Solid fuel cooking operations shall have spark arresters to minimize the passage
of airborne sparks and embers into plenums and ducts.
14.3.3
All solid fuel cooking equipment served by hood and duct systems shall be
separate from all other exhaust systems.
14.5.2
If airborne sparks and embers can be generated by the solid fuel cooking
operation, spark arrester devices shall be used prior to the grease removal
device to minimize the entrance of these sparks and embers into the grease
removal device and into the hood and duct system.
A.3.2.2 Authority
Having Jurisdiction The phrase is used in NFPA documents in a broad manner,
since jurisdictions and approval agencies vary, as do their responsibilities.
Where public safety is primary, the authority having jurisdiction may be a
federal, state, local, or other regional department or individual such as a fire
chief; fire marshal; chief of a fire prevention bureau, labor department, or
health department; building official; electrical inspector; or others having
statutory authority. For insurance purposes, an insurance inspection
department, rating bureau, or other insurance company representative may be the
authority having jurisdiction. In many circumstances, the property owner or
his or her designated agent assumes the role of the authority having
jurisdiction; at government installations, the commanding officer or
departmental official may be the authority having jurisdiction.
A.3.3.22.1 Grease
Filter. Filters
are expected to minimize the projection of flames downstream when attached by
flame on the upstream side and are expected to maintain their strength, shape,
and integrity when exposed to the anticipated rough handling, cleaning, and
service found in the field.
A.3.3.22.2 Mesh-Type
Filter. This type
of filter is not tested, listed, or acceptable for commercial cooking operations
due to the increased fire hazard.